Мобильная версия

Доступно журналов:

3 288

Доступно статей:

3 891 637

 

Скрыть метаданые

Автор Peter Bårmann
Автор Stefan Kröll
Автор Anders Sunesson
Дата выпуска 1997-03-07
dc.description Spatially and temporally resolved spectroscopic measurements of light emitted from positive streamers in transformer oil are presented. Analyses of the measurements performed with a DC needle - plane gap yield electron densities and indications of the atomic excitation temperatures in the streamers. The hydrogen emission reveals an electron density below during the main part of the streamer propagation time (80 - 90%). Later the light is also characterized by emission from a high-density plasma with electron densities in the range . The electron density during this time increases approximately linearly with distance from the initiation point and a density factor of four higher has been measured at the streamer tip than at the root. Measurements with high spectral resolution detect both high and low electron densities simultaneously. A tentative model of the interior of the streamer plasma, spatially resolved, is presented.
Формат application.pdf
Издатель Institute of Physics Publishing
Название Spatially and temporally resolved electron density measurements in streamers in dielectric liquids
Тип paper
DOI 10.1088/0022-3727/30/5/018
Electronic ISSN 1361-6463
Print ISSN 0022-3727
Журнал Journal of Physics D: Applied Physics
Том 30
Первая страница 856
Последняя страница 863
Выпуск 5

Скрыть метаданые